欧美老熟女一区二区-污视频在线观看一区二区-国产成人久久综合一区-久久精品久久国产视频-国产区精品视频-亚洲av日韩av永久无码下载-久久婷婷丁香综合-国产精品一区二区三区不卡-综合网在线视频-久久久久性色av毛片特级-欧美一级性

Hubei Dayu Hanguang Vacuum Electric Co.,Ltd.
CN EN

Embedded Poles

Model:EEP-24/3150-31.5

Category:Embedded poles


Product details

HEP-24 3150-31.5A-1.jpgHEP-24 3150-31.5A-2.jpg

HEP-24 3150-31.5A-4.jpg

Specifications of Embedded Pole

Main Technical SpecificationUnitSpecification
3150
Rated voltagekV24
Rated currentA3150
Rated frequencyHZ50/60
Short time power frequency withstand voltage(1min)kV65(79)
Lightning impulse withstand voltagekV125(145)
Rated short circuit breaking currentkA31.5
Rated peak withstand currentkA80
Rated short circuit making currentkA80
Rated short time withstand currentkA25
Rated duration of short circuitS4
Rated breaking current of single capacitor bankA400
Rated breaking current of back to back capacitor bankA400
Rated operating sequenceO-0.3s-CO180s-CO
Breaking operations of rated short circuit breaking currentTimes20
Rated mechanical enduranceTimes10000
Closing force due to bellow and atmosphereN100±50
Force required to hold contacts open at full strokeN200±50
Circuit resistance at lower limit of rated contact forcemΩ≤25
Contacts limit erosionmm3
Gas pressure inside vacuum interrupterPa≤1x10?3
Localize dischargePc≤5

Mechanical Data Required for the Matched Vacuum Switchgear

Main Technical SpecificationUnitSpecification
3150
Clearance between open contactsmm13±1
Average opening speedm/s1.3±0.2
Average closing speedm/s0.6±0.2
Rated of contact forceN3150±200
Contact bouncing duration at closing operationms≤2
Out of simultaneity of contact closing and openingms≤2
Maximum rebound during openingmm≤2